* The installation process can not pull the product's exposed wires , non-tossing, and should allow sufficient space for maintenance;
* When installing the heat meters, there should be 5 times straight pipe length in front and 3 times straight pipe length the behind

* Water meter per second to refresh the display, when detecting the meter, the valve should be closed at least 16 seconds before the reading (including the initial value and the end value), otherwise it will affect the detection results
* During use, if there is an abnormal problem (such as measurement is not working, etc.), please contact the relevant administrative departments, not to self-maintenance;
* Product design with a disposable tamper-evident seal, unauthorized persons can't remove it, or you will lose the right to get free service

· Quality Guarantee: Water meter for 1 year;

The loss caused by the leakage of the water supply pipe net is very alarming, especially when the pipeline bursts suddenly. After the pipe burst, the loss in one hour is as high as 1250 cubic meters of water. if it can't be repaired in time, the burst water will wash the ground and cause the road collapse, which will cause casualties and property losses.
·Technical data conform to international standard ISO 4064.
·Communication:rs485 Modbus,LoRa
·Low-power design and the use of high-energy batteries, can work for 8 years and more.
·The communication interface is Lora or Rs485, which can achieve remote real-time monitoring and management on the LAN.
·Threaded connection digital water meter, used in industrial pipelines, suitable for high-pressure environment, can choose whether to install pulse output
1. The ultrasonic water meter collects the flow in the pipeline, and the pressure data is uploaded to the cloud service platform through RTU.
2. Sudden change of alarm of pressure and flow.
1. High-range ratio ultrasonic water meter.accurate measurement.
2. Fast feedback and accurate positioning of emergency information.

Length L1 | Height H1 | |||||
d | D | |||||
DN15 | 258 | 165 | 95 | 95 | R1/R2 | G3/4B |
DN20 | 299 | 195 | 95 | 100 | R3/4 | G1B |
DN25 | 345 | 225 | 95 | 108 | R1 | G1 1/4B |
DN32 | 305 | 180 | 95 | 120 | R1 1/4 | G1 1/2B |
DN40 | 330 | 200 | 95 | 125 | R1 1/2 | G2B |
15 | 20 | 25 | 32 | 40 | ||
Q3/Q1 | R200 | |||||
Overload flow(Q4) | m³/h | 3.125 | 5 | 7.875 | 12.5 | 20 |
Nominal flow(Q3) | m³/h | 2.5 | 4 | 6.3 | 10 | 16 |
Transitional flow(Q2) | m³/h | 0.02 | 0.032 | 0.05 | 0.08 | 0.128 |
Minimum flow(Q1) | m³/h | 0.016 | 0.02 | 0.032 | 0.05 | 0.08 |
Class2 | ||||||
8years | ||||||
T30/T50 | ||||||
Less than or equal to 0.063Mpa | ||||||
ΔP68 | ||||||
U10/D5 | ||||||
Class B, M1 | ||||||
E1 | ||||||
1.6Mpa | ||||||
9999999.9 | ||||||